Specifications
|
Nominal voltage (V)
| 12 |
20-hr rate Capacity to 10.5V at 20°C (Ah)
| 17 |
10-hr rate Capacity to 10.8V at 20°C (Ah)
| 15.7 |
Dimensions
|
Length (mm)
| 181 (±1)
|
Width (mm)
| 76 (±1)
|
Height over terminals (mm)
| 167 (±2)
|
Mass (kg)
| 6.1
|
Terminal Type
|
Threaded terminal - (M=Male or F=Female)
| M5 (F)
|
Torque (Nm)
| 2.45
|
Operating Temperature Range
|
Storage (in fully charged condition)
| -20°C to +60°C
|
Charge
| -15°C to +50°C
|
Discharge
| -20°C to +60°C
|
Storage
|
Capacity loss per month at 20°C (% approx.)
| 3 |
Case Material
|
Standard
| ABS (UL94:HB)
|
FR version available
| UL94:V0
|
Charge Voltage
|
Float charge voltage at 20°C (V)/Block
| 13.65 (±1%)
|
Float charge voltage at 20°C (V)/Cell
| 2.275 (±1%)
|
Float Charge voltage temp correction factor from standard 20°C (mV)
| -3
|
Cyclic (or Boost) charge Voltage at 20°C (V)/Block
| 14.5 (±3%)
|
Cyclic (or Boost) charge Voltage at 20°C (V)/Cell
| 2.42 (±3%)
|
Cyclic Charge voltage temp correction factor from standard 20°C (mV)
| -4
|
Charge Current
|
Float charge current limit (A)
| No limit
|
Cyclic (or Boost) charge current limit (A)
| 4.25
|
Maximum Discharge Current
|
1 second (A)
| 500
|
1 minute (A)
| 150 |
Short-Circuit Current & Internal Resistance
|
Internal resistance - according to EN IEC 60896-21 (mO)
| 34.47
|
Short-Circuit current - according to EN IEC 60896-21 (A)
| 421
|
Impedance
|
Measured at 1 kHz (mO)
| 15 |
Design Life & Approvals
|
EUROBAT Classification: Standard Commercial
| 3 to 5 years
|
Yuasa design life at 20°C (yrs)
| up to 5
|