Riello UPS 240watts Approx runtime 1 hour 240WATTS APPROX RUNTIME 1 HOUR
Mouse over the image to zoom. Double-tap and hold to zoom.
Riello UPS
Riello UPS

Riello UPS 240watts Approx runtime 1 hour 240WATTS APPROX RUNTIME 1 HOUR

Product Code: ITM004029
UPC: 240watts Approx runtime 1 hour
Login to View Price
Online Availability
Quantity Available: 0
Availability: Out of stock
ModelsSDH 2200 A3
INPUT
Rated power2200 VA
Voltage220 / 230 / 240 V
Voltage tolerance230 V ±20%
Frequency50 / 60 Hz ±5
Frequency tolerance50 Hz ±5% / 60 Hz ±5%
Power factor>0.98
Current distortion=7%
BY PASS
Voltage tolerance200 / 253 V
Frequency toleranceFrequency selected (from ±0.5 Hz to ±5 Hz configurable)
OUTPUT and INVERTER OUTPUT
Rated power2200 VA
Active power1980 W
Crest factor (Ipeak/Irms)3:1
WaveformSinusoidal
FrequencySelectable: 50 Hz or 60 Hz or self-learning
Voltage distortion with non-linear load=3.5%
Voltage distortion with linear load<2%
OVERLOAD TIMES
Load = 150%0.5 sec
Load = 125%4 sec.
BATTERIES
TypeVRLA AGM maintenance-free lead based
Typical recharge time2-4 h
ENVIRONMENTAL
ColorBlack
CommunicationUSB / DB9 with RS232 and contacts / Slot for communications interface
Accessories providedPower cable, serial cable, USB cable, safety manual, quick start guide
Surge capability300 J
Line-Interactive/Smart Active efficiency98%
Noise (at 1 m)<40 [bBA] (ECO Mode)
Operating temperature0 °C - +40 °C
Relative humidity5-95% non-condensing
StandardsEuropean directives: L V 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility -- Directive and Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant -- Classification in accordance with IEC 62040-3 VFI - SS - 111
DATA
Weight30.5 kg
Dimensions (h w d)(T- 450x875x625) (R- 2Ux19€x425) mm
Documents