Input Specification | |
Voltage | 90-264Vac |
Frequency | 50-60Hz |
Max. Current | 10A |
Mains Input Fuse | 3.0A 250V |
Output Specification | |
Voltage | Nominal 27.6VDC when mains present |
Max. Load Current | 10A |
Ripple | 150mV pk-pk max |
Load output Fuse | 10A |
Overload Protection | Electronics shutdown until overload or short circuit removed (under mains power only) |
Standby Battery | |
Battery type | 24VDC Lead Acid |
Battery Capacity | 2 x DC12V7Ah |
Local Indicators | |
Fault LED | Red indicating output fuse fail or battery fuse fail |
Mains LED | Green indicating mains are normal |
Battery LED | Orange indicating battery is in charging. Green indicating battery is full charged. Red indicating battery is in discharging. |
Signalling Output | |
Lid &Rear Tamper | N/O volt free contact (NOTE: contact closed when fixed to the wall and lid closed.) |
Mains Fail Output Relay | N/O or N/C volt free output |
Environmental | |
Working Temperature | -10°C~+40°C |
Storage Temperature | -20°C ~+60°C |
Humidity | 95% RH non-condensing |
Box Size: | W360xH330xD90mm Clam Lid Box, for 2x7Ah Batteries |
Terminals | |
V+ | + voltage O/P to load equipment |
V - | - voltage O/P to load equipment |
B+ | Red lead to standby battery |
B - | Black lead to standby battery |
Tamper | x2 Tamper volt free contact |
N.C. | Relay close to com when mains presents (Open when no mains) |
COM | Common terminal of Mains Fail Output Relay |
N.O. | Relay open to com when mains presents (Close when no mains) |
Documents |
---|