Input Specification | |
Voltage | 90-264Vac |
Frequency | 50-60Hz |
Max. Current | 1A, 2A or 3A |
Mains Input Fuse | 3.0A 250V |
Max. Standby Power | 0.5W (no load and no battery connected) |
Output Specification | |
Voltage | 13.4-14.2Vdc (13.8Vdc nominal) on mains power 10.0-12.3Vdc on battery standby |
Max. Load Current | 1.0A |
Ripple | 150mV pk-pk max. |
Load output Fuse | 1A Overload Protection Electronics shutdown until overload or short circuit removed (under mains power only) |
Standby Battery | |
Battery type | 12VDC Lead Acid |
Battery Capacity | 7Ah |
Battery Charging Fuse | 1.0A |
Local Indicators | |
MAINS LED | (green) Mains Present |
FAULT LED | (red) Fault present: Output fuse fail or battery fuse fail |
Signaling Output | |
Lid &Rear Tamper | N/O volt free contact NOTE: contact closed when both the PSU is fixed to the wall and lid closed. |
Dimensions | |
Box Size | 200x240x75mm (W x H x D, Removable Hinged Lid, for 1x7Ah) |
Environmental | |
Working Temperature | -10„ƒ~+40„ƒ |
Storage Temperature | -20„ƒ~+60„ƒ |
Humidity | 95% RH non-condensing |
Terminals | |
V+ | + voltage O/P to load equipment |
V - | - voltage O/P to load equipment |
B+ | Red lead to standby battery |
B - | Black lead to standby battery |
Tamper x2 | Tamper volt free contact |
Compliance | |
This power supply unit meets the essential requirements of the following European Directives: | Low Voltage 2006/95/EC EMC 2004/108/EC WEEE 2002/96/EC RoHS 2002/95/EC |