C-TEC CFP704-2 AlarmSense 4-Zone Two-Wire Fire Alarm Panel
Mouse over the image to zoom. Double-tap and hold to zoom.
C-Tec
C-Tec

C-TEC CFP704-2 AlarmSense 4-Zone Two-Wire Fire Alarm Panel

Product Code: ITM002040
UPC: CFP704-2
Login to View Price
Online Availability
Quantity Available: 0
Availability: Out of stock
Specification
Approvals/certifications Certified to EN54-2 & 4 by the LPCB.
Mains supply 230V 50/60Hz.
Mains rated current 350mA maximum.
Internal power supply 19V-28.5V (27V nominal). Ripple 7V maximum (battery fault).
Total output current limited to 1.5A @ 230Vac (ImaxA eq 146mA).
Quiescent current
25mA (mains failed, internal sounder active, PSU & gen fault LED lit).
Max battery size and type
2 x 12V 3.2Ah VRLA connected in series. Min. battery size 1.2Ah.
No. of detector zone circuits
The CFP704-2 has 4 AlarmSense zone circuits which are compatible with Apollo's AlarmSense range of detectors & call points AND sounders & visual indicators. (Max. length per circuit is 500m).
Call point resistor value
Only use AlarmSense call points.
Max. devices per detector zone
25 AlarmSense detectors/manual call points per AlarmSense zone. For AlarmSense sounder limitations per AlarmSense zone see 'Max. sounder output current' section.
No. of conventional sounder circuits
4 - these are additional conventional (non-AlarmSense) sounder circuits; Max. length per circuit is 500m.
EOL resistor value
6800O 5% Tol. 0/25W (blue, grey, red, gold).
Alarm voltage
27V max, 20V min (final battery voltage).
Max. sounder output current
Each AlarmSense zone circuit & each conventional sounder circuit will support a max. sounder current of 200mA. Distribute sounder loads as evenly as possible. Total sounder loading per panel should not exceed 1.25A.
Auxiliary relays
Two: (1) Aux. Fire; (2) Fault. Volt free single pole changeover. Max. switch current 1A; Max. switch voltage 30Vdc.
Open collector outputs
Two: (1) Reset (Active during reset cycle); (2) Remote (Active during any unsilenced fire condition provided all relevant delays have expired). Max. sink current 30mA, Max. open circuit voltage 27Vdc).
Other outputs
24V Aux. Power (Protected by a resettable fuse. 100mA min. hold current. Resets when fault removed).
Auxiliary inputs
Two: (1) €˜Class Change€™ (constant sounders); (2) Alert (pulsed sounders). Connect to 0V to trigger, Max. input voltage 27V (non-latching).
Engineer (AL3) functions
Program coincidence (double knock); Invoke One Man Walk Test; Program delays; Set up zones for non-latching operation; Program sounders to resound (or not resound) when a new zone enters alarm; Enter fault diagnostic facilities.
Expansion connections
Yes - for optional network driver cards (one required per repeater system), relay output cards and EN54-13 sounder circuit interface boards.
Product dimensions (mm)
380 W x 235 H x D 96mm.
Construction & finish
Plastic lid and base; RAL7035 textured.
IP Rating
IP30.
Weight 1.75kg without batteries.
Product dimensions 367 W x 235 H x 96 D mm.
Hole required for flush mounting 367 W x 220 H x 75 D mm. No bezel required.

You May Also Be Interested In

List of suggested products: You May Also Be Interested In.
Apollo 55000-190APO AlarmSense A1R Heat Detector
Apollo 55000-190APO AlarmSense A1R Heat Detector
Code: ITM002855
Login to View Price
Quantity Available: 2
Availability: In stock
Yuasa NP3.2-12 12V 3.2Ah Sealed Lead Acid Rechargeable Battery
Yuasa NP3.2-12 12V 3.2Ah Sealed Lead Acid Rechargeable Battery
Code: ITM002511
Login to View Price
Quantity Available: 12
Availability: In stock
Our website requires cookies to enhance your online browsing experience. For example, these cookies allow you to save products in your shopping cart, even when you’re not logged into your account. These cookies are crucial for ensuring the website functions correctly.