C-TEC CFP702-4 Standard 2-Zone Fire Alarm Panel
Mouse over the image to zoom. Double-tap and hold to zoom.
C-Tec
C-Tec

C-TEC CFP702-4 Standard 2-Zone Fire Alarm Panel

Product Code: ITM002039
UPC: CFP702-4
Login to View Price
Online Availability
Quantity Available: 1
Availability: In stock
Specification
Approvals/certificationsCertified to EN54-2/4 by the LPCB (176b) / (0832-CPD-1704).
Mains supply230V 50/60Hz.
Mains rated current350mA maximum.
Internal power supply19V-28.5V (27V nominal). Ripple 7V maximum (battery fault).
Total output current limited to1.5A @ 230Vac (ImaxA eq 146mA).
Quiescent current25mA (mains failed, internal sounder active, PSU & gen fault LED lit).
Max battery size and type2 x 12V 3.2Ah VRLA connected in series. Min. battery size 1.2Ah.
No. of detector zone circuits2 (Max. length per circuit is 500m).
Call point resistor value470 to 680O.
Max. devices per detector zone25 detectors (or 32 detectors/manual call points combined).
No. of conventional sounder circuits4 (Max. length per circuit is 500m).
EOL resistor value6800O 5% Tol. 0/25W (blue, grey, red, gold).
Alarm voltage27V max, 20V min (final battery voltage).
Max. sounder output current4 x 200mA (800mA total).
Auxiliary relaysTwo: (1) Aux. Fire; (2) Fault. Volt free single pole changeover. Max. switch current 1A; Max. switch voltage 30Vdc.
Open collector outputsTwo: (1) Reset (Active during reset cycle); (2) Remote (Active during any unsilenced fire condition provided all relevant delays have expired). Max. sink current 30mA, Max. open circuit voltage 27Vdc)
Other outputs24V Aux. Power (Protected by a resettable fuse. 100mA min. hold current. Resets when fault removed).
Auxiliary inputsTwo: (1) €˜Class Change€™ (constant sounders); (2) Alert (pulsed sounders). Connect to 0V to trigger, Max. input voltage 27V (non-latching)
Engineer (AL3) functionsProgram coincidence (double knock); Invoke One Man Walk Test; Program delays; Set up zones for non-latching operation; Program sounders to resound (or not resound) when a new zone enters alarm; Enter fault diagnostic facilities
Expansion connectionsYes - for optional network driver cards (one required per repeater system), relay output cards and EN54-13 sounder circuit interface boards.
Product dimensions (mm)380 W x 235 H x D 96mm.
Construction & finishPlastic lid and base; RAL7035 textured.
IP RatingIP30.
Weight1.75kg (without batteries).
Operating conditions/temperature-5ºC to +40ºC. Max relative humidity: 95%.
Product dimensions:380 W x 235 H x 96 D mm.
Hole required for flush mounting:367 W x 220 H x 75 D mm. No bezel required.