Ajax FireProtect 2+ RB (White) Advanced Smoke and Temperature Detector with Battery
Mouse over the image to zoom. Double-tap and hold to zoom.
Ajax
Ajax

Ajax FireProtect 2+ RB (White) Advanced Smoke and Temperature Detector with Battery

Product Code: ITM000985
UPC: FIREPROTECT2+/RB(WHITE) - 52252.137.WH1
Login to View Price
Online Availability
Quantity Available: 7
Availability: In stock
Compatibility
Hubs
Hub Plus
Hub 2 (2G)
Hub 2 (4G)
Hub 2 Plus
Hub Hybrid (2G)
Hub Hybrid (4G)
Radio signal range extenders
ReX
ReX 2
Communication
Jeweller communication technology
Proprietary wireless technology for transmission of alarms and events.

Features:
  • Two-way communication.
  • Protection against device spoofing.
  • Block encryption featuring a floating key.
  • Instant notifications.
  • Remote configuration via the Ajax apps.
Frequency bands
866.0 - 866.5 MHz
868.0 - 868.6 MHz
868.7 - 869.2 MHz
905.0 - 926.5 MHz
915.85 - 926.5 MHz
921.0 - 922.0 MHz
Maximum effective radiated power (ERP)
up to 20 mW

Automatic power control to reduce power consumption and radio interference.
Radio signal modulation
GFSK
Radio communication range
up to 1,700 m

Between the detector and a hub (or radio signal range extender) in an open space.
Encryption of radio communication
All the data stored and transmitted are protected by block encryption with a floating key.
Radio frequency hopping
To prevent radio interference and jamming.
Sensitive elements
Sensitive elements
smoke sensor

temperature sensor

CO (carbon monoxide) sensor
Smoke detection
Sensitive element
double-spectrum optical sensor

Recognizes smoke by the size of particles in the air.
Protection from false alarms
Does not react to water vapour
Patented smoke chamber
Protects the smoke sensor from dust, dirt, and insects.
Dangerous temperature detection
Sensitive element
according to the requirements for Class A1 temperature detectors

Requirements of EN 54-5 and BS 5446-2 standards.
High temperature alarm
at temperatures above 64°C
Temperature spike alarm
when the temperature rises more than 10°C in 1 minute or less
Carbon monoxide (CO) detection
Sensitive element
chemical CO sensor
Alarm if accumulated dose of CO is exceeded
more than 50 ppm (0.005%) - no more than in 90 minutes
more than 100 ppm (0.01%) - no more than in 40 minutes
more than 300 ppm (0.03%) - no more than in 3 minutes
CO concentration of 400 ppm (0.04%) within 3 hours can be life-threatening. The detector stops notifying about the dangerous level of carbon monoxide when the concentration drops to 50 ppm (0.005%) within one minute.
Sensor life
10 years

After 10 years of operation, the detector must be replaced with a new one.
Additional features
In-built siren
volume 85 dB at a distance of 3 meters

Sound notification of alarms. Active until the reason for triggering is eliminated or until the user disables notification.
Interconnected Fire Detectors Alarms
All fire detectors in the system turn on built-in sirens if at least one of the detectors registers an alarm. An interconnected fire alarm is activated during one €œhub - detector€ polling interval but no more than 20 seconds later.
LED indication
green is a power indication

A LED indicator on the device enclosure lights up once every 56 seconds. The indication meets the requirements of EN 50291.
yellow is an indication of malfunctions

A LED indicator on the device enclosure lights up when malfunctions are detected. For example, in the case of discharged batteries, contamination of the smoke chamber, or end of the service life.
red is an indication of fire alarms

A LED indicator on the device enclosure lights up when the detector registers a fire alarm.
Button on the front panel of the detector
In normal mode, when pressed, it starts the smoke chamber test. In the event of an alarm or malfunction, the pressing turns off the detector sound notification.
Recommendations
The device is designed only for indoor installation.
SmartBracket mounting panel allows adjusting the position of the detector after installation.
Anti-sabotage protection
Tampering alarm
Alerts of attempts to detach the detector from the surface or remove the mounting panel.
Protection against spoofing
device authentication
Detection of communication failure
within 15 minutes

The time to detect communication loss depends on the settings for the number of undelivered data packages (specified in the Jeweller or Jeweller/Fibra settings). The polling interval is fixed at 300 seconds
Power supply
For FireProtect 2 RB (Heat/Smoke)
2 non-replaceable lithium batteries
10 years of battery life.
Enclosure
Dimensions
124 x 124 x 45 mm
Weight
270 g
Operating temperature range
from 0°Ð¡ to +50°Ð¡
Operating humidity
up to 80%
Protection class
IP20
Colours
Black or white
Complete set
FireProtect 2 SB (Heat/Smoke/CO) Jeweller
SmartBracket mounting panel
Installation kit
Quick Start Guide
Our website requires cookies to enhance your online browsing experience. For example, these cookies allow you to save products in your shopping cart, even when you’re not logged into your account. These cookies are crucial for ensuring the website functions correctly.